Service of a Conventional Fire Panel as per SANS 10139 Clause 12 Maintenance:

Purpose & Frequency of Service:

  • Servicing a fire detection system does not constitute a review of system design; it is a verification of the functionality of the existing system.
  • Accordingly, it is not necessarily the case that non-compliance with this standard will be identified at the time of routine servicing, particularly if the original design is not available.
    • Any such advice provided to the user by IBR Fire cannot be regarded (by users, enforcing authorities or any other party) as an implication that the maintenance technician has identified, or has endeavoured to identify, all such areas of non-compliance, or that there has been any review of the original design.
  • The period between successive inspection and servicing visits should not exceed 6 months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this standard.

12.2.4 Recommendations for inspection and testing of the Detection system over a 12-month period:

The work described may be carried out over two or more services in 12 months.

  • All automatic fire detectors should be functionally tested.
    • The tests used need to prove only that the detectors are connected to the system and are operational.
    • Where fitted, detector remote indicators should also be checked for correct operation.
    • Record manufacturing dates (10-year life span as per manufacturer specification)
  • All fire alarm devices should be checked for correct operation.
  • Radio signal strengths in radio-linked systems to which 8.20 applies should be checked for adequacy and the results recorded
  • Confirm 24 Hour Remote Monitoring is Active and Functional
  • Location Descriptions checked for accuracy
  • Confirm Class B Wiring with the correct placement of the End-of-Line Resistor per SANS 10139 and Manufacturer Specifications.
  • The owner should check the standby power supply capacity to confirm the suitability of continued service.
  • Confirm a suitable zone plan of the premises is provided on or adjacent to all control and indicating equipment and repeat indicating equipment.
    • Where repeat indicating equipment relates to only part of the premises, the adjacent zone plan need only relate to that part of the premises.
  • Confirm availability of handover documentation per SANS 10139 Clause 11:
    • Certificate of Design
    • Certificate of Installation
    • Certificate of Commissioning
    • Certificate of Verification
    • ?Certificate of Acceptance
    • Operation and Maintenance Manuals
    • Equipment Data Sheets
    • Drawings are available and current showing. Location & number of detectors / MCPs / Sounder Beacons / Interface Units / Isolators / Cable Routes & Zones

On completion of the above Service work:

  • A Maintenance Certificate will be provided by your Sales Representative.
  • Rectification Report & Quotation will be provided by a Technical Consultant based on:
    • Maintaining the functionality of the existing Detection System
    • Obtaining a Certificate of Compliance to SANS 10139

Exclusions:

Testing, Cleaning, Alignment Programming or Repairs of

  • Beams
  • Aspirating fire detection systems
  • Carbon monoxide fire detectors
  • Flame detectors
  • Multi-sensor detectors
  • Lifting Equipment
  • Testing of the Alarm sound pressure level after hours unless otherwise specified.

CATALOGUE NAME : Systems (Supply and Install) - Technical Consultants Only
CATEGORY : Industrial

Service of a Conventional Fire Panel as per SANS 10139 Clause 12 Maintenance:

Purpose & Frequency of Service:

  • Servicing a fire detection system does not constitute a review of system design; it is a verification of the functionality of the existing system.
  • Accordingly, it is not necessarily the case that non-compliance with this standard will be identified at the time of routine servicing, particularly if the original design is not available.
    • Any such advice provided to the user by IBR Fire cannot be regarded (by users, enforcing authorities or any other party) as an implication that the maintenance technician has identified, or has endeavoured to identify, all such areas of non-compliance, or that there has been any review of the original design.
  • The period between successive inspection and servicing visits should not exceed 6 months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this standard.

12.2.4 Recommendations for inspection and testing of the Detection system over a 12-month period:

The work described may be carried out over two or more services in 12 months.

  • All automatic fire detectors should be functionally tested.
    • The tests used need to prove only that the detectors are connected to the system and are operational.
    • Where fitted, detector remote indicators should also be checked for correct operation.
    • Record manufacturing dates (10-year life span as per manufacturer specification)
  • All fire alarm devices should be checked for correct operation.
  • Radio signal strengths in radio-linked systems to which 8.20 applies should be checked for adequacy and the results recorded
  • Confirm 24 Hour Remote Monitoring is Active and Functional
  • Location Descriptions checked for accuracy
  • Confirm Class B Wiring with the correct placement of the End-of-Line Resistor per SANS 10139 and Manufacturer Specifications.
  • The owner should check the standby power supply capacity to confirm the suitability of continued service.
  • Confirm a suitable zone plan of the premises is provided on or adjacent to all control and indicating equipment and repeat indicating equipment.
    • Where repeat indicating equipment relates to only part of the premises, the adjacent zone plan need only relate to that part of the premises.
  • Confirm availability of handover documentation per SANS 10139 Clause 11:
    • Certificate of Design
    • Certificate of Installation
    • Certificate of Commissioning
    • Certificate of Verification
    • ?Certificate of Acceptance
    • Operation and Maintenance Manuals
    • Equipment Data Sheets
    • Drawings are available and current showing. Location & number of detectors / MCPs / Sounder Beacons / Interface Units / Isolators / Cable Routes & Zones

On completion of the above Service work:

  • A Maintenance Certificate will be provided by your Sales Representative.
  • Rectification Report & Quotation will be provided by a Technical Consultant based on:
    • Maintaining the functionality of the existing Detection System
    • Obtaining a Certificate of Compliance to SANS 10139

Exclusions:

Testing, Cleaning, Alignment Programming or Repairs of

  • Beams
  • Aspirating fire detection systems
  • Carbon monoxide fire detectors
  • Flame detectors
  • Multi-sensor detectors
  • Lifting Equipment
  • Testing of the Alarm sound pressure level after hours unless otherwise specified.

Service of a Conventional Fire Panel as per SANS 10139 Clause 12 Maintenance:

Purpose & Frequency of Service:

  • Servicing a fire detection system does not constitute a review of system design; it is a verification of the functionality of the existing system.
  • Accordingly, it is not necessarily the case that non-compliance with this standard will be identified at the time of routine servicing, particularly if the original design is not available.
    • Any such advice provided to the user by IBR Fire cannot be regarded (by users, enforcing authorities or any other party) as an implication that the maintenance technician has identified, or has endeavoured to identify, all such areas of non-compliance, or that there has been any review of the original design.
  • The period between successive inspection and servicing visits should not exceed 6 months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this standard.

12.2.4 Recommendations for inspection and testing of the Detection system over a 12-month period:

The work described may be carried out over two or more services in 12 months.

  • All automatic fire detectors should be functionally tested.
    • The tests used need to prove only that the detectors are connected to the system and are operational.
    • Where fitted, detector remote indicators should also be checked for correct operation.
    • Record manufacturing dates (10-year life span as per manufacturer specification)
  • All fire alarm devices should be checked for correct operation.
  • Radio signal strengths in radio-linked systems to which 8.20 applies should be checked for adequacy and the results recorded
  • Confirm 24 Hour Remote Monitoring is Active and Functional
  • Location Descriptions checked for accuracy
  • Confirm Class B Wiring with the correct placement of the End-of-Line Resistor per SANS 10139 and Manufacturer Specifications.
  • The owner should check the standby power supply capacity to confirm the suitability of continued service.
  • Confirm a suitable zone plan of the premises is provided on or adjacent to all control and indicating equipment and repeat indicating equipment.
    • Where repeat indicating equipment relates to only part of the premises, the adjacent zone plan need only relate to that part of the premises.
  • Confirm availability of handover documentation per SANS 10139 Clause 11:
    • Certificate of Design
    • Certificate of Installation
    • Certificate of Commissioning
    • Certificate of Verification
    • ?Certificate of Acceptance
    • Operation and Maintenance Manuals
    • Equipment Data Sheets
    • Drawings are available and current showing. Location & number of detectors / MCPs / Sounder Beacons / Interface Units / Isolators / Cable Routes & Zones

On completion of the above Service work:

  • A Maintenance Certificate will be provided by your Sales Representative.
  • Rectification Report & Quotation will be provided by a Technical Consultant based on:
    • Maintaining the functionality of the existing Detection System
    • Obtaining a Certificate of Compliance to SANS 10139

Exclusions:

Testing, Cleaning, Alignment Programming or Repairs of

  • Beams
  • Aspirating fire detection systems
  • Carbon monoxide fire detectors
  • Flame detectors
  • Multi-sensor detectors
  • Lifting Equipment
  • Testing of the Alarm sound pressure level after hours unless otherwise specified.